|























| |
Systems Designed in cooperation with DaimlerChrysler
Technical Center, Auburn Hills Michigan
CHRYSLER TECHNICAL CENTER UNIVERSAL DOOR INTERFACE SYSTEM
CATALOG NO. CU2DFI

THE ULTIMATE RELAY LOGIC CONTROL SYSTEM
DESIGNED SPECIFICALLY FOR THE AUBURN HILLS TECHNICAL CENTER.
One Standard Control Panel Operates All Types of
Doors
As of November 1998, over 160 units are in operation in the
Auburn Hills Facility
This control system is designed to standardize the operation
of all motorized door inside the Chrysler Headquarters & Technical Center.
It’s unique design enables Building Management the flexibility to offer each
tenant any control options they like without special modifications to the
control panel.
The basic interface system is installed on the door,
providing standard Open, Close, Stop pushbuttons functions, as well as the
standard reversing door edge. Once the tenant moves in, the desired accessories
are installed by building management per the tenant’s requirements.
This system is endorsed by the facilities Electrical Trades.
The graphics display inside the panel as well as the push to test diagnostic
system enables a tradesman familiar with the panel to diagnose any door problems
by visual inspection of the panel.
The interface system is designed to operate sectional doors,
rolling steel doors, fabric doors, sliding door, folding doors, gates, grilles,
glass doors, etc., with single speed, two speed, variable speed AC motors, as
well as DC motors.
This control panel is designed for UL & CSA approval.
Standard features built into the interface system include:
 | NEMA 12 Enclosure |
 | Size 30" High x 24" Wide x 8" Deep |
 | Powder Coated Finish blends in with building colors and does not need
painting. |
 | Lockable rotary fused disconnect |
 | Touch Safe High Voltage Disconnect Switch |
 | Class J Rejection type fuses in disconnect |
 | Pushbuttons & Pilot lights - 22MM size |
 | Open-Close-Stop Pushbuttons located on panel face. |
 | Keyed selector for Automatic/Off/Manual operation included on
panel face. |
 | Reversing Edge Tripped and Reset pilot light located on panel face. |
 | Overload Tripped pilot light on panel face. |
 | Prepared for 120 V & 24 V accessories |
 | Transformers have fused Primary & Secondary circuits. |
 | Prepared for Plug In Timer to Close |
 | Spare Terminals provided for up to 3 remote stop pushbuttons. |
 | Pre-wired for all types of remote open devices. |
 | Pre-wired for all type of reversing devices, with fail safe wiring design. |
 | Pre-wired for single button activation systems. |
 | Delay Reverse Circuitry fixed at 1.5 sec. |
 | Circuitry designed for easy visual diagnostics. Each limit switch
and accessory drives a push-to-test pilot light relay, enabling the
electricians to visibly see conditions of inputs without any test equipment. |
 | |
 | Basic control circuitry and components remain the same with various
motor styles. Design incorporates control of single speed, two speed,
variable frequency, DC drives, without changing the basic control circuit.
All basic diagnostics remain the same. |
 | Seven Digit Non-Resettable cycle counter. |
 | Prepared for two door vestibule interlocking |
 | Contacts for activating door heater standard. |
 | Contacts for remote door indication, such as door fully open or
closed standard. |
 | Class 20 Motor overloads standard, with output wired to pilot light on
panel face, indicating tripped condition. |
 | Remote brake operation is included where required for either standard
braking or instantaneous braking. |
 | Provisions for DC braking. |
 | Provisions for Thru-Beam or Retro-Reflective photo-eyes |
 | Pre-wired block for plug-in loop detector. |
 | Concrete loop terminals pre-wired. |
 | Prepared to two, three or four wire reversing edges. |
 | Prepared for Motor Run timer |
 | Prepared for advance open limit switches |
 | Snow limit switch provisions included. |
 | Prepared for all type of hand chain & crank disconnects. |
 | Prepared for break-away door system interlocks. |
 | Plug in socket for headlight sensor activator |
Standard accessories for the control panels include:
 | Automatic Timer to Close - Plug in timer automatically closes the
door after a set time period. This is turned on and off by the standard Auto /
Hand keyed selector switch. |
 | Card Reader / Security Connections for Existing Building Security System.
Terminals are provided so the existing Thorn security system can tie into and
control the door system. |
 | Loop Detectors - standard panel is prepared for one Shrokman 120
VAC plug in self tuning loop detector. |
 | Remote 3 button stations- standard panel is prepared to accept two
remote push button stations without modification. |
 | Radio Controls - prepared for Shrokman Single Button, Two Button
& Three Button radio control receivers. Sequence of operations varies via
terminal connections inside the control panel. |
 | Pull Cords - terminals provided for two separate sequences. |
 | Motion Sensors - provisions provided to have the motion sensors
operate for standard automatic operation or as safety only devices. |
 | Vehicle Presence Sensor - unique system senses presence of
vehicles in opening. System in most cases does not sense pedestrians. |
 | Headlight Sensor - Mounted on the door, this unit activates the
door by flashing the headlights on any vehicle. This is a plug in accessory. |
 | Smart Post - Guard posts that include photo-eyes and presence
sensors for automatic opening or safety. |
DOOR TYPES CURRENTLY BEING OPERATED BY THE CU2DFI CONTROL
SYSTEM:
Rolling Steel Fire Doors
Rolling Steel Service Doors
Sectional Overhead doors
Sliding Doors
Megadoor Vertical Lifting Fabric
M & I Fabric Doors
Gate Operators
MOTOR TYPES:
Single Speed (Standard)
Two Speed (Option)
Inverter Motors (Option)
DC (Option)
MAIN LINE VOLTAGE: 460 Volts
PHASE: 3 Phase
MOTOR SIZE: 1/3 TO 5 H.P.
BRAKE: Full Voltage (std) & prewired for remote braking -
standard or instantaneous.
DC (Option)
LIMIT SWITCH REQUIREMENTS:
1 (QTY) Normally Closed Open Limit Switch
1 (QTY) Normally Closed Close Limit Switch
Prepared to accept as standard:
N.C. Advance Open Limit
N.C. Advance Close Limit
REVERSING EDGE REQUIREMENTS
Electric - 2 wire, 3 wire, 4 wire (Standard)
Pneumatic - 2 wire N.O. or N.C.
UNIVERSAL DOOR CONTROL PANEL
FOR USE ON ALL MOTORIZED DOORS.
CHRYSLER CORPORATION
AUBURN HILLS CORPORATE HEADQUARTERS
AUBURN HILLS, MICHIGAN
SECTION 08370
POWER-OPERATED DOOR CONTROLS
PART 1 - GENERAL
- REFERENCES
- - NFPA 70 - National Electrical Code (NEC).
- - NFPA 79 - Electrical Standard for Industrial Machinery
- - UL 508A - Underwriters Laboratories Inc.
- - IEC 529, IEC 947-1
- - CSA - C22.2 Special Industrial Control Assemblies
1.02 SUBMITTALS
- Submit manufacturer’s catalog information regarding the application of
this special control panel.
- Shop Drawings
- Submittals to include wiring schematics as well as riser diagrams for
each type of door used in the facility, including dimensions and wiring
diagram for each type of operator.
- All accessories that can be wired into the system must be included in
the submittal.
- Submittals must include wiring diagrams for each type of motor
operation listed below.
- Maintenance Instructions
- Submit maintenance and troubleshooting instructions for control
panels.
- Provide training classes for Chrysler personnel on application and use
of control panels.
PART 2 - PRODUCTS
MANUFACTURERS: Advanced Systems Inc., Birmingham Michigan 48009 Attn:
Dan McDonald 734-449-8876 Advanced Systems Tennessee
Engineering Office, Hendersonville Tennessee 37075 Attn: George Shrokman
615-826-5559
Control panel shall be designed to operate all types of upward acting doors
used in the facility, and incorporate circuitry that enables the tenant in each
area to modify the operation of the door system without completely wiring the
control panel. The design shall incorporate expansion capabilities for various
types of motors and drive accessories. Relay Logic panels shall include pilot
light diagnostics for all internal components.
2.01 CONTROL EQUIPMENT
- POWER
- Control panels shall be prepared for connection to a 460V Three Phase
power source.
- ENCLOSURE - Hammond 2R30248 or owner approved equal.
- NEMA 12 rated, "Design Line" style enclosure, 30" high x
30" wide x 8" deep.
- Doors must be designed to be easily removed and interchanged.
- Compression stops installed to insure optimum gasket performance.
- Minimum of two slotted quarter turn oil-tight latches secure the door,
with a minimum of one key lock installed in the top latch position. Key
lock to match existing control panel keying.
- Cover and enclosure are phosphatized, primed and finished.
- Enclosure will have expansion room for additional motor circuitry
required for two speed motors, Variable frequency drives, as well as
special motor braking systems.
- DISCONNECT - Bussman CF30 with BDH99 Handle or owner approved equal.
- Disconnect rating - 30 AMP, with Class J Rejection Fuses.
- NEMA 12 rated Pistol handle.
- Handle is lockable with three padlocks
- 30 AMP double break contacts
- provide terminal shrouds & fuse covers for "touch-sage"
protection.
- DISCONNECT FUSING - Bussman "Low-Peak Yellow" Fuses or owner
approved equal.
- Provide main fusing in disconnect for proper operation per NEC & UL.
- Dual-Element, Time-Delay -- 10 Seconds (minimum) at 500% rated current.
- Interrupting rating - 300,000A RMS SYM. (U.L.)
- TRANSFORMERS - Square D Type K or owner approved equal.
- Machine tool grade transformers.
- 10 year transformer warranty.
- Minimum 150 VA for 120 VAC circuitry
- Minimum 100 VA for 24 VAC circuitry.
- One side of the transformer shall be grounded.
- TRANSFORMER FUSING - Bussman Products
- Provide 600 V rated fusing for transformer primary circuits.
- Provide 250V rated fusing for all transformer secondary circuits.
- MOTOR CONTACTORS - Square D / Telemecanique D-Line or owner approved
equal.
- Contacts rated 5 HP at 460 VAC
- AC3 rating - 9 amps, AC1 rating 20 AMPS
- 24 VAC coil voltage, with coil wire insulation rated at 180 degree
centigrade.
- Top Mounted Auxiliary Contacts
- Insulation Voltage - 1000 V
- IP 20 Fingersafe Terminal Protection.
- THERMAL OVERLOAD RELAYS - Square D / Telemecanique D-line or owner
approved equal.
- Adjustable overload to be sized per motor application.
- Mounted directly below motor starter.
- Separate Stop and reset functions with switchable manual or automatic
reset.
- Trip test button on the front cover with protected lockable indicator.
- Manual/auto reset selector and setting dial cover can be sealed against
tampering from original setting.
- Provide isolated NO and NC contacts (600 V Insulation) for wiring to
"Overload Tripped" pilot light on panel face.
- CONTROL RELAYS - Square D Type KU - Spade Terminals
- Provide relay with Manual Operator to speed circuit testing, allowing
the relay to be manually switched to simulate normal operation.
- Provide Neon Internal Pilot Light indication to show when the relay is
energized.
- Industry Standard wiring and pin arrangements.
- 10 AMP Contact Rating
- TIMERS - Square D - Class 9050 - Type JCK
- Provide Timers as required in the control system to make door operate as
required.
- Contact Raging - 10 AMP
- DPDT Contacts ( 2 NO and 2 NC)
- Transient Protected.
- AUXILIARY SOCKET FOR LOOP DETECTOR - Square D - Class 9050
- Provide an 11 pin socket, prewired for installation of loop detector.
- PUSH BUTTONS - Square D -XB series 22MM
- NEMA 4 - 4X rating
- Color per NFPA 79
- Metallic guard around operator head
- PILOT LIGHTS - Square D - XB2 - 22 MM
- NEMA 4 - 4X rating
- Push-to-Test type
- Metallic guard around operator head
- SELECTOR SWITCHES - Square D - XB2 - 22MM
- NEMA 4 - 4X rating
- Metallic guard around operator head
- WIRING DUCT - Gould - Gray - 1" x 3" with round holes.
- TERMINAL BLOCKS - Square D - Class 9080
- 600 V - 50 AMP Rating
- "Touch-Safe" Design
-
- WIRE
- Colors per NFPA 79
- Black - Line, load, and control circuits at line voltage.
- Red - AC control circuits at less than line voltage.
- Blue - DC control circuits.
- Yellow - Interlock control circuits supplied from an external power
source.
- Green - Equipment grounding conductor.
- White - Grounded circuit conductor.
CONTROL SYSTEM DESIGN PARAMETERS
The control panel shall incorporate into the standard circuitry provisions to
operate any upward acting door in the facility.
The control panel shall incorporate the following features.
- MOTOR TYPES
- Standard control panel shall have provisions for operation of single speed
460V Three Phase motors.
- Two speed motors can be used with the addition of the required contactors,
without modifying the basic secondary control circuits.
- Variable frequency drives can be substituted in the panel without
modifying the basic secondary control circuits.
- MOTOR BRAKE SYSTEMS
- Standard control panel shall have provisions at the terminal strip for
three types of brake operations.
- Standard solenoid or line voltage brake used on slow moving types of
doors.
- Standard DC or AC braking, used with single speed or two speed brake
motors.
- Instantaneous braking of DC or AC brake, used with single and two speed
motors, as well as variable frequency drive units.
- RELAY LOGIC WITH DIAGNOSTICS
- Panel design will provide visual diagnostics inside the control panel.
- Each limit switch on the drive will drive a separate relay, which has
pilot light and push to test capabilities.
- Each relay will be labeled with the function, and pilot light sequence.
- Labels shall provide diagnostic functions at each position.
- LIMIT SWITCH DIAGNOSTICS
- Each limit switch on the door operator shall drive a pilot indicator
light, showing the limit switch condition.
- A push button inside the control panel shall enable maintenance personnel
to check the operation of the limit switch without running jumper wires.
- All control panels will have provisions for five limit switches.
- Supervision Limit Switch(Chain hoist, Break-Away, Hand Crank, Main
Limit, Etc.)
- Door Full Open Limit Switch
- Advance Open Limit Switch
- Advance Close Limit Switch
- Door Full Closed Limit Switch
- REVERSING EDGE RESET AND PILOT LIGHT
- A Push-to-Test pilot light and reset button indicating the reversing edge
has tripped shall be mounted on the face of the control panel.
- When the reversing edge has been tripped, the door will stop, pilot light
on panel face will energize, and The door will go to the fully open
position. The door will remain there until the reset button located on the
panel face is pressed.
- Provide circuit design so the reversing edge circuit can be checked by
pressing a test button inside the control panel..
- STANDARD AND FAIL-SAFE REVERSING EDGE CIRCUITRY
- Control circuitry will provide installation and operation of the standard
facility reversing edges or fail safe design reversing edges via
installation of one jumper wire at a terminal block location.
- Circuitry will be such that the Pilot light and reset button on the panel
face shall work for both types of edges.
- AUXILIARY PUSH BUTTONS
- The terminal strip shall contain provisions for at least two remote stop
pushbuttons in the control circuit, as well as the panel face stop button.
- Provisions shall be made for installation of remote open and close
buttons.
- DELAY TO REVERSE CIRCUIT
- Each panel shall have a delay to reverse circuit with adjustable time of
.1 to 1.9 seconds.
- As the door is closing, and any reversing or activation device is
activated, the door shall stop, the timer will activate and time out, and
then send the door to the fully open position.
- Circuitry shall be tied in with the brake circuitry to enable proper brake
operation.
- DOOR POSITION INDICATION
- Provide terminals at the terminal strip to indicate the door fully open or
fully closed.
- Contacts for each position - 1 NO and 1 NC
- OVERLOAD TRIPPED PILOT LIGHT
- Provide pilot light indication on face of control panel to indicate when
the thermal motor overload is in a tripped position.
- Pilot light is to be push to test design.
- Circuit design to incorporate remote reset capabilities for future
expansion and tie in with remote PLC systems, such as AGV’s, etc.
- MAIN CONTROL CIRCUIT VOLTAGE
- The main control circuit shall be operated at 24VAC to help reduce shock
hazard.
- Terminals shall be provided at the main terminal strip for access to 24
VAC for accessories.
- AUXILIARY DEVICE VOLTAGE PROVISIONS
- Provide a 120 VAC transformer in the circuit for accessory adaption.
- Terminals shall be provided for access to 120 VAC power for accessories.
- HAND / AUTO SELECTOR SWITCH
- Provide a selector switch on the panel face for sequencing as per the
"Sequence of Operations" section.
SEQUENCE OF OPERATIONS
- Power on - Selector Switch in HAND position.
- Door Fully Closed
- Momentary contact on the Open push button sends the door to the fully
open position.
- Momentary Contact open/close devices send the door to the fully open
position.
- Automatic open/timed close devices have no effect.
- External reversing devices have no effect
- Door Fully Open
- Momentary pressure on the close pushbutton starts the door closed.
- Momentary Contact open/close devices start the door closed.
- Automatic open/timed close devices have no effect.
- External reversing devices have no effect
- Door Moving Closed
- Momentary pressure on the stop button immediately stops the door.
- Open button has no effect
- Momentary Contact Open/Close devices stop, delay and reverse the door
to the fully open position.
- External reversing devices stop, delay and reverse the door to the
fully open position.
- Automatic open/timed close devices have no effect.
- Power on - Selector Switch in AUTO position.
- Door Fully Closed
- Momentary contact on the Open push button sends the door to the fully
open position.
- Momentary Contact Open/Close devices send the door to the fully open
position.
- Automatic Open/Timed Close devices send the door to the fully open
position.
- External reversing devices have no effect.
- Door Fully Open
When the door reaches the fully open position, and the open limit switch
is tripped, an automatic close timer is energized.
- Momentary contact on the Close push button sends the door down.
- Momentary Contact Open/Close devices send the door to down.
- Automatic Open/Timed Close devices reset the automatic close timer,
and the cycle begins timing from 0 seconds..
- External reversing devices reset the automatic close timer, and the
timing cycle begins timing from 0 seconds..
- Door Moving Closed
- Momentary pressure on the stop button immediately stops the door.
- Open button has no effect.
- Momentary Contact Open/Close devices stop, delay and reverse the door
to the fully open position.
- External reversing devices stop, delay and reverse the door to the
fully open position.
- Automatic Open/Timed Close devices stop, delay and reverse the door to
the fully open position.
- Reversing door edge stops, delays and reverse the door to the fully
open position. NOTE: The door will not automatically close until the
Reversing edge reset button is pressed.
STANDARD METHODS OF OPERATIONS
The standard interface system has many sequences built in to the control
panel. Below is a description and usage of many of them.
- Standard Control Panel Methods of Operations Descriptions Built Into the
Panel
- Open: Pushbutton on control panel face
Auto Mode Only: Automatic Open Devices
- Close: Pushbutton on control panel face
Auto Mode Only: None
- Safety Devices: Reversing Door Edge
- Standard Accessories Methods of Operation Description.
- Hand Mode Open:
- Remote Open Pushbutton
- Auto Mode Open:
- Motion Sensor
- Presence Sensor
- Loop Detector
- Security Provided Card Reader
- Headlight Sensor
- Radio Transmitter
- Hand Mode Close:
- Remote Close Pushbutton
- Auto Mode Close:
- Close Delay Timer
USAGE AND SEQUENCE DESCRIPTIONS
Basic Features not mentioned below.
- There is a Hand/Off/Auto selector switch on the control panel face. Off
turns the complete system off without turning off the power.
- Security: Each panel is prepared for:
- An input from security enabling the door to be shut off by security when
required. (Wiring from control panel to security panel should be specified
in the Security Specifications and not his section)
- A signal can be sent to security when the door is fully closed.
- A signal can be sent to security when the power to the door control
panel is turned off.
- Basic Door - Controlled from panel only.
- Method of Operation (#).
- Ingress, 24-hour , unlocked:
- Open: Pushbutton on panel face
- Close: Pushbutton on panel face
- Egress: 24-hour, unlocked:
- Open: Pushbutton on panel face
- Close: Pushbutton on panel face
- Safety Devices:
- Safety edge, contact type
-
- Basic Door - Controlled from panel and remote 3 button station located
inside secured area.
- Method of Operation (#).
- Ingress, 24-hour , unlocked:
- Open: Pushbutton on control panel face in secured area
- Close: Pushbutton on panel face in secured area
- Egress: 24-hour, unlocked:
- Open: Pushbutton on panel face & remote push button in secured
area
- Close: Pushbutton on panel face & remove push button in secured
area
- Safety Devices:
- Safety edge, contact type
- Basic Door - Controlled from panel and remote 3 button station located on
the unsecured side.
- Method of Operation (#).
- Ingress, 24-hour , unlocked:
- Open: Pushbutton on control panel face in secured area & remote
push button in unsecured area
- Close: Pushbutton on panel face in secured area & remote push
button in unsecured area
- Egress: 24-hour, unlocked:
- Open: Pushbutton on panel face
- Close: Pushbutton on panel face
- Safety Devices:
- Safety edge, contact type
- Automatic Closing Door - NOTE: Building Management requires two safety
devices on all doors that have any type of automatic closing.
Opens from both sides.
- Method of Operation (#)
- Ingress, 24-hour , unlocked:
- Open: Pushbutton on control panel face in secured area
- Open: Auto Mode Only: Automatic Open Devices - Loop Detector (LD) (or
name other devices)
- Close: Pushbutton on panel face in secured area
- Close: Auto Mode Only: Close delay timer.
- Egress: 24-hour, unlocked:
- Open: Pushbutton on panel face
- Open: Auto Mode Only: Automatic Open Devices - Loop Detector (LD) (or
name other devices)
- Close: Pushbutton on panel face
- Close: Auto Mode Only: Close delay timer.
- Safety Devices:
- Safety edge, contact type
- Photo-eyes: Thru-beam type mounted on opposite side of door on wall.
Opens from inside (secured area) only.
- Method of Operation (#)
- Ingress, 24-hour , unlocked:
- Open: Pushbutton on control panel face in secured area
- Close: Pushbutton on panel face in secured area
- Close: Auto Mode Only: Close delay timer.
- Egress: 24-hour, unlocked:
- Open: Pushbutton on panel face
- Open: Auto Mode Only: Automatic Open Devices - Loop Detector (LD) (or
name other devices)
- Close: Pushbutton on panel face
- Close: Auto Mode Only: Close delay timer.
- Safety Devices:
- Safety edge, contact type
- Photo-eyes: Thru-beam type mounted on opposite side of door on wall.
DCTC PLC Logic Specification
DaimlerChrysler PLC Standard Panel
SECTION 08370-B
DOOR SYSTEM CONTROL PANEL
PART 1 - GENERAL
- SUMMARY
- Scope
- Provide Control Panel that will incorporate all components necessary to
properly operate the doors at each door opening. Provide accessories, and
incidental work, as shown and specified.
- All electrical equipment and construction specified in this SECTION
shall conform to established governing standards and codes, and to
applicable requirements of DIVISION 16 of the SPECIFICATIONS.
- Related Work Specified Under Other Sections
- High Speed Stacking Overhead Flexible Doors
- Steel framed door openings - DIVISION 5.
- Provision of a single 480 volt, 3 phase electrical power source to the
main disconnect switch at the door control panel - DIVISION 16.
- SUBMITTALS
- Furnish submittals for items that are identified in this SECTION by a
different typeface and a bracketed code (e.g. item [L]). Refer to
SECTION 01340 for definition of codes for types of submittals and the
administrative requirements governing submittal procedure. Additional
submittal requirements pertaining to this SECTION are specified herein under
this Article.
- Submit completely detailed shop drawings showing all components and
installation work to be provided. Include complete information on electric
motor operation, wiring diagrams and controls.
- Submit manufacturers product data covering operating instructions and
maintenance data for the control system.
PRODUCT DELIVERY, STORAGE AND HANDLING
- Wrap and crate materials and finished work adequately, considering
climate changes and shipping methods.
- Deliver products in undamaged condition, in manufacturer’s original
containers or packaging, with identifying labels intact and legible.
- Upon delivery, immediately inspect shipments to assure their compliance
with the requirements of the CONTRACT DOCUMENTS and approved submittals,
and that the products are properly protected and undamaged. Report damaged
or defective items. Remove broken, damaged, or unlabeled items from the
site immediately.
- Store products in accordance with manufacturer’s instructions, with
seals and labels intact and legible. Store products in a manner to prevent
damage, soiling, theft, deterioration, and contamination. Marred surfaces,
cracked, checked, split, or warped materials will be rejected. Sore
products subject to damage by the elements in weather tight enclosures.
Maintain temperature and humidity within the ranges required by the
manufacturer.
- Repair, or clean items that have been damaged or soiled that can be
restored. The OWNER’S REPRESENTATIVE shall be the judge of the
effectiveness of remedial measures. Additional time required to secure
replacements and to make repairs will not be considered by the OWNER’S
REPRESENTATIVE to justify an extension in the CONTRACT time of completion.
PROTECTION
- Protect the work during installation from mechanical damage, scratching
or marring, soiling, contamination, deterioration, and theft.
- Maintain protection during subsequent work operations, and remove same
upon OWNER’S REPRESENTATIVE acceptance or when instructed by the OWNERS
REPRESENTATIVE.
QUALITY ASSURANCE
- Manufacturer shall warrant control panel mechanical and electrical
components against defects in materials and workmanship for one year
beginning with the date of substantial Completion.
REFERENCES
- NFPA 70 - National Electrical Code (NEC).
- NFPA 79 - Electrical Standard for Industrial Machinery
- UL 508A - Underwriters Laboratories Inc.
- IEC 529, IEC 947-1
- CSA - C22.2 Special Industrial Control Assemblies
SUBMITTALS
- Submit manufacturer’s catalog information regarding the application of
this special control panel.
Shop Drawings
- Submittals to include wiring schematics as well as riser diagrams for
each type of door used in the facility, including dimensions and wiring
diagram for each type of operator.
- All accessories that can be wired into the system must be included in
the submittal.
- Submittals must include wiring diagrams for each type of motor operation
listed below.
Maintenance Instructions
- Submit maintenance and troubleshooting instructions for control panels.
- Provide training classes for Chrysler personnel on application and use
of control panels.
PART 2 - PRODUCTS
- MANUFACTURERS:
Advanced Systems Inc., Birmingham Michigan 48009
Attn: Dan McDonald 734-449-8876 Advanced Systems
Tennessee Engineering Office, Hendersonville Tennessee 37075 Attn:
George Shrokman 615-826-5559
Control panel shall be designed to operate the upward acting doors on the
drawings. Each door shall have an inside and outside floor loop, as well as an
inside and outside mounted photo-eye. The door heater motor starter and
appropriate inputs and outputs for proper heater operation shall be included
in this panel. The design shall incorporate expansion capabilities for various
types of motors and drive accessories. PLC logic will be utilized, and the
system will tie into the existing Building Automation System.
CONTROL EQUIPMENT
POWER
Control panels shall be prepared for connection to a 460V Three Phase power
source.
ENCLOSURE - Hammond 2R30248 or owner approved equal.
- NEMA 12 rated, "Design Line" style enclosure, 30" high x
30" wide x 8" deep.
- Doors must be designed to be easily removed and interchanged.
- Compression stops installed to insure optimum gasket performance.
- Minimum of two slotted quarter turn oil-tight latches secure the door,
with a minimum of one key lock installed in the top latch position. Key lock
to match existing control panel keying.
- Cover and enclosure are phosphatized, primed and finished.
- Enclosure will have expansion room for additional motor circuitry required
for two speed motors, Variable frequency drives, as well as special motor
braking systems.
DISCONNECT - Bussman CF30 with BDH99 Handle or owner approved equal.
- Disconnect rating - 30 AMP, with Class J Rejection Fuses.
- NEMA 12 rated Pistol handle.
- Handle is lockable with three padlocks
- 30 AMP double break contacts
- provide terminal shrouds & fuse covers for "touch-sage"
protection.
DISCONNECT FUSING - Bussman "Low-Peak Yellow" Fuses or owner
approved equal.
- Provide main fusing in disconnect for proper operation per NEC & UL.
- Dual-Element, Time-Delay -- 10 Seconds (minimum) at 500% rated current.
- Interrupting rating - 300,000A RMS SYM. (U.L.)
TRANSFORMERS - Square D Type K or owner approved equal.
- Machine tool grade transformers.
- 10 year transformer warranty.
- Minimum 150 VA for 120 VAC circuitry
- Minimum 100 VA for 24 VAC circuitry.
- One side of the transformer shall be grounded.
TRANSFORMER FUSING - Bussman Products
- Provide 600 V rated fusing for transformer primary circuits.
- Provide 250V rated fusing for all transformer secondary circuits.
INTEGRAL SELF PROTECTED MOTOR STARTERS - Square D / Telemecanique
- Contacts rated 10 HP at 460 VAC
- Current Rating - 18 Amp
- 24 VAC coil voltage, with coil wire insulation rated at 180 degree
centigrade.
- Auxiliary contacts to send status to PLC.
- Auto - Ready for Operation
- Off - Breaker turned off
- Tripped by Any Fault
- Tripped by Short Circuit
- Insulation Voltage - 1000 V
- IP 20 Finger safe Terminal Protection.
PLC - Johnson Controls Model DX9100
Provide proper base unit and all expansion components to operate all the
desired equipment.
PLC Program to be prepared by Johnson Controls.
Provide all components for expansion to directly tie into existing building
automation system
AUXILIARY SOCKET FOR LOOP DETECTOR - Square D - Class 9050
- Provide an 11 pin socket, prewired for installation of loop detector.
PUSH BUTTONS - Square D -XB series 22MM
- NEMA 4 - 4X rating
- Color per NFPA 79
- Metallic guard around operator head
PILOT LIGHTS - Square D - XB2 - 22 MM
- NEMA 4 - 4X rating
- Push-to-Test type
- Metallic guard around operator head
SELECTOR SWITCHES - Square D - XB2 - 22MM
- NEMA 4 - 4X rating
- Metallic guard around operator head
WIRING DUCT - Gould - Gray - 1" x 3" with round holes.
TERMINAL BLOCKS - Square D - Class 9080
- 600 V - 50 AMP Rating
- "Touch-Safe" Design
WIRE
Colors per NFPA 79
- Black - Line, load, and control circuits at line voltage.
- Red - AC control circuits at less than line voltage.
- Blue - DC control circuits.
- Yellow - Interlock control circuits supplied from an external power
source.
- Green - Equipment grounding conductor.
- White - Grounded circuit conductor.
CONTROL SYSTEM DESIGN PARAMETERS
- The control panel shall incorporate into the standard circuitry provisions
to operate any upward acting door in the facility.
- The control panel shall incorporate the following features.
- MOTOR TYPES
- Standard control panel shall have provisions for operation of single speed
460V Three Phase motors.
- Two speed motors can be used with the addition of the required contactors,
without modifying the basic secondary control circuits.
- Variable frequency drives can be substituted in the panel without
modifying the basic secondary control circuits.
MOTOR BRAKE SYSTEMS
Standard control panel shall have provisions at the terminal strip for
three types of brake operations.
Standard solenoid or line voltage brake used on slow moving types of
doors.
Standard DC or AC braking, used with single speed or two speed brake
motors.
Instantaneous braking of DC or AC brake, used with single and two speed
motors, as well as variable frequency drive units.
PLC LOGIC WITH DIAGNOSTICS
Panel design will provide visual diagnostics inside the control panel.
Each limit switch, push button and other activation devices will have a
separate input.
INPUTS
Each limit switch on the door operator shall be wired to a separate input.
All control panels will have provisions for six limit switch inputs.
Push Buttons
- Door Opne
- Door Close
- Door Stop
Selector Switches
- Auto - Hand - Off
Limit Switches.
- Hand Crank
- Door Over Travel 1
- Door Over Travel 2
- Door Closed 1
- Door Closed 2
- Door Full Open NO
- Door Full Open NC
Misc.
- Overload Tripped Door
- Overload Tripped Heater
Outputs
Coils
- Motor Open
- Motor Close
- Motor Brake
- Heater Motor
- Heater Solenoids
Pilot lights
- Overload Tripped
- Reversing Edge Tripped
REVERSING EDGE RESET AND PILOT LIGHT
A Push-to-Test pilot light and reset button indicating the reversing edge
has tripped shall be mounted on the face of the control panel.
When the reversing edge has been tripped, the door will stop, pilot light
on panel face will energize, and The door will go to the fully open
position. The door will remain there until the reset button located on the
panel face is pressed.
Provide circuit design so the reversing edge circuit can be checked by
pressing a test button inside the control panel..
AUXILIARY PUSH BUTTONS
The terminal strip shall contain provisions for at least two remote stop
pushbuttons in the control circuit, as well as the panel face stop button.
Provisions shall be made for installation of remote open and close
buttons.
MAIN CONTROL CIRCUIT VOLTAGE
The main control circuit shall be operated at 24VAC to help reduce shock
hazard.
Terminals shall be provided at the main terminal strip for access to 24
VAC for accessories.
AUXILIARY DEVICE VOLTAGE PROVISIONS
Provide a 120 VAC transformer in the circuit for accessory adaption.
Terminals shall be provided for access to 120 VAC power for accessories.
HAND / AUTO SELECTOR SWITCH
Provide a selector switch on the panel face for sequencing as per the
"Sequence of Operations" section.
SEQUENCE OF OPERATIONS
Basic Sequence of Operations
- Power on - Selector Switch in HAND position.
- Door Fully Closed
- Momentary contact on the Open push button sends the door to the fully
open position.
- Momentary Contact open/close devices send the door to the fully open
position.
- Automatic open/timed close devices have no effect.
- External reversing devices have no effect
- Door Fully Open
- Momentary pressure on the close pushbutton starts the door closed.
- Momentary Contact open/close devices start the door closed.
- Automatic open/timed close devices have no effect.
- External reversing devices have no effect
- Door Moving Closed
- Momentary pressure on the stop button immediately stops the door.
- Open button has no effect
- Momentary Contact Open/Close devices stop, delay and reverse the door
to the fully open position.
- External reversing devices stop, delay and reverse the door to the
fully open position.
- Automatic open/timed close devices have no effect.
- Power on - Selector Switch in AUTO position.
- Door Fully Closed
- Momentary contact on the Open push button sends the door to the fully
open position.
- Momentary Contact Open/Close devices send the door to the fully open
position.
- Automatic Open/Timed Close devices send the door to the fully open
position.
- External reversing devices have no effect.
- Door Fully Open
When the door reaches the fully open position, and the open limit switch
is tripped, an automatic close timer is energized.
- Momentary contact on the Close push button sends the door down.
- Momentary Contact Open/Close devices send the door to down.
- Automatic Open/Timed Close devices reset the automatic close timer,
and the cycle begins timing from 0 seconds..
- External reversing devices reset the automatic close timer, and the
timing cycle begins timing from 0 seconds..
- Door Moving Closed
- Momentary pressure on the stop button immediately stops the door.
- Open button has no effect.
- Momentary Contact Open/Close devices stop, delay and reverse the door
to the fully open position.
- External reversing devices stop, delay and reverse the door to the
fully open position.
- Automatic Open/Timed Close devices stop, delay and reverse the door to
the fully open position.
- Reversing door edge stops, delays and reverse the door to the fully
open position. NOTE: The door will not automatically close until the
Reversing edge reset button is pressed.
EXECUTION
- PAINTING
- Shop prime paint all exposed ferrous surfaces of the control panel.
- Shop prime paint all exposed parts of all types of operators, cabinets,
safety switches, push button stations, and other items which are provided
with an acceptable paint or enameled finish by the manufacturer, will need
no further painting. However, handle such items in a manner that the
finish is not marred or damaged.
- Bonderize all exposed galvanized surfaces, or apply galvanized metal
primer, as standard with the manufacturer, so that surfaces are in proper
condition to received field painting. Apply one coat of rust inhibiting
metal primer, as standard with the manufacturer, on all other exposed
ferrous metal surfaces, so that surfaces are in proper condition to
receive field painting.
- INSPECTION
- Inspect the Work in place and notify the OWNER’S REPRESENTATIVE of
defects in the work of the other trades that will affect the proper
installation or function of the Work of this SECTION. Starting the Work
shall constitute acceptance of the adjoining work and conditions a the
site under which the work is to be done.
- Installation
- Install control panels and provide all electrical wiring from the
devices controlled by the system.
- Secure control panel to wall plumb, level and in line. Provide
additional support as necessary for attachment.
- Connect and adjust electrical components and operating hardware. 460
Volt feed to wall mounted control panel by other electrical trades.
- Upon completion of installation, including work by other trades, verify
equipment operation with the equipment manufacturers.
- FIELD QUALITY CONTROL
After the complete system is installed, test-demonstrate in the presence of
the OWNER’S REPRESENTATIVE, that the system operates properly under all
conditions and in proper sequence.
DaimlerChrysler Chelsea
DAIMLERCHRYSLER PROVING GROUNDS UNIVERSAL DOOR INTERFACE SYSTEM
CATALOG NO. CU1DFI

THE ULTIMATE RELAY LOGIC CONTROL SYSTEM
DESIGNED SPECIFICALLY FOR THE CHELSEA PROVING GROUNDS.
One Standard Control Panel Operates All Types of
Doors
This control system is designed to standardize the operation
of all motorized door inside the DaimlerChrysler Proving Grounds. It’s unique
design enables Building Management the flexibility to offer each tenant any
control options they like without special modifications to the control panel.
The basic interface system is installed on the door,
providing standard Open, Close, Stop pushbuttons functions, as well as the
standard reversing door edge. Once the tenant moves in, the desired accessories
are installed by building management per the tenant’s requirements.
This system is endorsed by the facilities Electrical Trades.
The graphics display inside the panel as well as the push to test diagnostic
system enables a tradesman familiar with the panel to diagnose any door problems
by visual inspection of the panel.
The interface system is designed to operate sectional doors,
rolling steel doors, fabric doors, sliding door, folding doors, gates, grilles,
glass doors, etc., with single speed, two speed, variable speed AC motors, as
well as DC motors.
This control panel is designed for UL & CSA Approvals.
Standard features built into the interface system include:
 | NEMA 12 Enclosure |
 | Size 30" High x 24" Wide x 8" Deep |
 | Powder Coated Finish blends in with building colors and does not need
painting. |
 | Lockable rotary fused disconnect |
 | Touch Safe High Voltage Disconnect Switch |
 | Class J Rejection type fuses in disconnect |
 | Pushbuttons & Pilot lights - 22MM size |
 | Open-Close-Stop Pushbuttons located on panel face. |
 | Keyed selector for Automatic/Off/Manual operation included on
panel face. |
 | Reversing Edge Tripped and Reset pilot light located on panel face. |
 | Overload Tripped pilot light on panel face. |
 | Prepared for 120 V & 24 V accessories |
 | Transformers have fused Primary & Secondary circuits. |
 | Prepared for Plug In Timer to Close |
 | Spare Terminals provided for up to 3 remote stop pushbuttons. |
 | Pre-wired for all types of remote open devices. |
 | Pre-wired for all type of reversing devices, with fail safe wiring design. |
 | Pre-wired for single button activation systems. |
 | Delay Reverse Circuitry fixed at 1.5 sec. |
 | Circuitry designed for easy visual diagnostics. Each limit switch
and accessory drives a push-to-test pilot light relay, enabling the
electricians to visibly see conditions of inputs without any test equipment. |
 | |
 | Basic control circuitry and components remain the same with various
motor styles. Design incorporates control of single speed, two speed,
variable frequency, DC drives, without changing the basic control circuit.
All basic diagnostics remain the same. |
 | Seven Digit Non-Resettable cycle counter. |
 | Prepared for two door vestibule interlocking |
 | Contacts for activating door heater standard. |
 | Contacts for remote door indication, such as door fully open or
closed standard. |
 | Class 20 Motor overloads standard, with output wired to pilot light on
panel face, indicating tripped condition. |
 | Remote brake operation is included where required for either standard
braking or instantaneous braking. |
 | Provisions for DC braking. |
 | Provisions for Thru-Beam or Retro-Reflective photo-eyes |
 | Pre-wired block for plug-in loop detector. |
 | Concrete loop terminals pre-wired. |
 | Prepared to two, three or four wire reversing edges. |
 | Prepared for Motor Run timer |
 | Prepared for advance open limit switches |
 | Snow limit switch provisions included. |
 | Prepared for all type of hand chain & crank disconnects. |
 | Prepared for break-away door system interlocks. |
 | Plug in socket for headlight sensor activator |
Standard accessories for the control panels include:
 | Automatic Timer to Close - Plug in timer automatically closes the
door after a set time period. This is turned on and off by the standard Auto /
Hand keyed selector switch. |
 | Card Reader / Security Connections for Existing Building Security System.
Terminals are provided so the existing Thorn security system can tie into and
control the door system. |
 | Loop Detectors - standard panel is prepared for one Shrokman 120
VAC plug in self tuning loop detector. |
 | Remote 3 button stations- standard panel is prepared to accept two
remote push button stations without modification. |
 | Radio Controls - prepared for Shrokman Single Button, Two Button
& Three Button radio control receivers. Sequence of operations varies via
terminal connections inside the control panel. |
 | Pull Cords - terminals provided for two separate sequences. |
 | Motion Sensors - provisions provided to have the motion sensors
operate for standard automatic operation or as safety only devices. |
 | Vehicle Presence Sensor - unique system senses presence of
vehicles in opening. System in most cases does not sense pedestrians. |
 | Headlight Sensor - Mounted on the door, this unit activates the
door by flashing the headlights on any vehicle. This is a plug in accessory. |
 | Smart Post - Guard posts that include photo-eyes and presence
sensors for automatic opening or safety. |
DOOR TYPES CURRENTLY BEING OPERATED BY THE CU1DFI CONTROL
SYSTEM:
Rolling Steel Fire Doors
Rolling Steel Service Doors
Sectional Overhead doors
Sliding Doors
Megadoor Vertical Lifting Fabric
M & I Fabric Doors
Gate Operators
MOTOR TYPES:
Single Speed (Standard)
Two Speed (Option)
Inverter Motors (Option)
DC (Option)
MAIN LINE VOLTAGE: 460 Volts
PHASE: 3 Phase
MOTOR SIZE: 1/3 TO 5 H.P.
BRAKE: Full Voltage (std) & prewired for remote braking -
standard or instantaneous.
DC (Option)
LIMIT SWITCH REQUIREMENTS:
1 (QTY) Normally Closed Open Limit Switch
1 (QTY) Normally Closed Close Limit Switch
Prepared to accept as standard:
N.C. Advance Open Limit
N.C. Advance Close Limit
REVERSING EDGE REQUIREMENTS
Electric - 2 wire, 3 wire, 4 wire (Standard)
Pneumatic - 2 wire N.O. or N.C.
UNIVERSAL DOOR CONTROL PANEL
FOR USE ON ALL MOTORIZED DOORS.
DAIMLERCHRYSLER CORPORATION
CHELSEA PROVING GROUNDS
CHELSEA, MICHIGAN
SECTION 08370
POWER-OPERATED DOOR CONTROLS
PART 1 - GENERAL
- REFERENCES
- - NFPA 70 - National Electrical Code (NEC).
- - NFPA 79 - Electrical Standard for Industrial Machinery
- - UL 508A - Underwriters Laboratories Inc.
- - IEC 529, IEC 947-1
- - CSA - C22.2 Special Industrial Control Assemblies
1.02 SUBMITTALS
- Submit manufacturer’s catalog information regarding the application of
this special control panel.
- Shop Drawings
- Submittals to include wiring schematics as well as riser diagrams for
each type of door used in the facility, including dimensions and wiring
diagram for each type of operator.
- All accessories that can be wired into the system must be included in
the submittal.
- Submittals must include wiring diagrams for each type of motor
operation listed below.
- Maintenance Instructions
- Submit maintenance and troubleshooting instructions for control
panels.
- Provide training classes for Chrysler personnel on application and use
of control panels.
PART 2 - PRODUCTS
MANUFACTURERS: Advanced Systems Inc., Birmingham Michigan 48009 Attn:
Dan McDonald 734-449-8876 Advanced Systems Tennessee
Engineering Office, Hendersonville Tennessee 37075 Attn: George Shrokman
615-826-5559
Control panel shall be designed to operate all types of upward acting doors
used in the facility, and incorporate circuitry that enables the tenant in each
area to modify the operation of the door system without completely wiring the
control panel. The design shall incorporate expansion capabilities for various
types of motors and drive accessories. Relay Logic panels shall include pilot
light diagnostics for all internal components.
2.01 CONTROL EQUIPMENT
- POWER
- Control panels shall be prepared for connection to a 460V Three Phase
power source.
- ENCLOSURE – Saginaw SCE-30EL2408LP or owner approved equal.
- NEMA 12 rated, "Design Line" style enclosure, 30" high x
24" wide x 8" deep.
- Doors must be designed to be easily removed and interchanged.
- Compression stops installed to insure optimum gasket performance.
- Minimum of two slotted quarter turn oil-tight latches secure the door,
with a minimum of one key lock installed in the top latch position. Key
lock to match existing control panel keying.
- Cover and enclosure are phosphatized, primed and finished.
- Enclosure will have expansion room for additional motor circuitry
required for two speed motors, Variable frequency drives, as well as
special motor braking systems.
- DISCONNECT - Square D 9421-NC3 with NW2 Handle or owner approved
equal.
- Disconnect rating - 30 AMP, with Class J Rejection Fuses.
- NEMA 4/4X rated Selector handle.
- Handle is lockable with three padlocks
- 30 AMP double break contacts
- provide terminal shrouds & fuse covers for "touch-sage"
protection.
- DISCONNECT FUSING - Bussman "Low-Peak Yellow" Fuses or owner
approved equal.
- Provide main fusing in disconnect for proper operation per NEC & UL.
- Dual-Element, Time-Delay -- 10 Seconds (minimum) at 500% rated current.
- Interrupting rating - 300,000A RMS SYM. (U.L.)
- TRANSFORMERS - Square D Type K or owner approved equal.
- Machine tool grade transformers.
- 10 year transformer warranty.
- Minimum 150 VA for 120 VAC circuitry
- Minimum 100 VA for 24 VAC circuitry.
- One side of the transformer shall be grounded.
- TRANSFORMER FUSING - Bussman Products
- Provide 600 V rated fusing for transformer primary circuits.
- Provide 250V rated fusing for all transformer secondary circuits.
- MOTOR CONTACTORS - Square D / Telemecanique D-Line or owner approved
equal.
- Contacts rated 5 HP at 460 VAC
- AC3 rating - 9 amps, AC1 rating 20 AMPS
- 24 VAC coil voltage, with coil wire insulation rated at 180 degree
centigrade.
- Top Mounted Auxiliary Contacts
- Insulation Voltage - 1000 V
- IP 20 Fingersafe Terminal Protection.
- THERMAL OVERLOAD RELAYS - Square D / Telemecanique D-line or owner
approved equal.
- Adjustable overload to be sized per motor application.
- Mounted directly below motor starter.
- Separate Stop and reset functions with switchable manual or automatic
reset.
- Trip test button on the front cover with protected lockable indicator.
- Manual/auto reset selector and setting dial cover can be sealed against
tampering from original setting.
- Provide isolated NO and NC contacts (600 V Insulation) for wiring to
"Overload Tripped" pilot light on panel face.
- CONTROL RELAYS - Square D Type KU - Spade Terminals
- Provide relay with Manual Operator to speed circuit testing, allowing
the relay to be manually switched to simulate normal operation.
- Provide Neon Internal Pilot Light indication to show when the relay is
energized.
- Industry Standard wiring and pin arrangements.
- 10 AMP Contact Rating
- TIMERS - Square D - Class 9050 - Type JCK
- Provide Timers as required in the control system to make door operate as
required.
- Contact Raging - 10 AMP
- DPDT Contacts ( 2 NO and 2 NC)
- Transient Protected.
- AUXILIARY SOCKET FOR LOOP DETECTOR - Square D - Class 9050
- Provide an 11 pin socket, prewired for installation of loop detector.
- PUSH BUTTONS - Square D - Oil tight 30MM - Series 9001
- NEMA 4 - 4X rating
- Color per NFPA 79
- Metallic guard around operator head
- PILOT LIGHTS - Square D - Oil tight 30MM - Series 9001
- NEMA 4 - 4X rating
- Push-to-Test type
- Metallic guard around operator head
- SELECTOR SWITCHES - Square D - Oil tight 30MM - Series 9001
- NEMA 4 - 4X rating
- Metallic guard around operator head
- WIRING DUCT - Gould - Black - 1" x 3" with round holes.
- TERMINAL BLOCKS - Square D - Class 9080
- 600 V - 50 AMP Rating
- "Touch-Safe" Design
-
- WIRE
- Colors per NFPA 79
- Black - Line, load, and control circuits at line voltage.
- Red - AC control circuits at less than line voltage.
- Blue - DC control circuits.
- Yellow - Interlock control circuits supplied from an external power
source.
- Green - Equipment grounding conductor.
- White - Grounded circuit conductor.
CONTROL SYSTEM DESIGN PARAMETERS
The control panel shall incorporate into the standard circuitry provisions to
operate any upward acting door in the facility.
The control panel shall incorporate the following features.
- MOTOR TYPES
- Standard control panel shall have provisions for operation of single speed
460V Three Phase motors.
- Two speed motors can be used with the addition of the required contactors,
without modifying the basic secondary control circuits.
- Variable frequency drives can be substituted in the panel without
modifying the basic secondary control circuits.
- MOTOR BRAKE SYSTEMS
- Standard control panel shall have provisions at the terminal strip for
three types of brake operations.
- Standard solenoid or line voltage brake used on slow moving types of
doors.
- Standard DC or AC braking, used with single speed or two speed brake
motors.
- Instantaneous braking of DC or AC brake, used with single and two speed
motors, as well as variable frequency drive units.
- RELAY LOGIC WITH DIAGNOSTICS
- Panel design will provide visual diagnostics inside the control panel.
- Each limit switch on the drive will drive a separate relay, which has
pilot light and push to test capabilities.
- Each relay will be labeled with the function, and pilot light sequence.
- Labels shall provide diagnostic functions at each position.
- LIMIT SWITCH DIAGNOSTICS
- Each limit switch on the door operator shall drive a pilot indicator
light, showing the limit switch condition.
- A push button inside the control panel shall enable maintenance personnel
to check the operation of the limit switch without running jumper wires.
- All control panels will have provisions for five limit switches.
- Supervision Limit Switch(Chain hoist, Break-Away, Hand Crank, Main
Limit, Etc.)
- Door Full Open Limit Switch
- Advance Open Limit Switch
- Advance Close Limit Switch
- Door Full Closed Limit Switch
- REVERSING EDGE RESET AND PILOT LIGHT
- A Push-to-Test pilot light and reset button indicating the reversing edge
has tripped shall be mounted on the face of the control panel.
- When the reversing edge has been tripped, the door will stop, pilot light
on panel face will energize, and The door will go to the fully open
position. The door will remain there until the reset button located on the
panel face is pressed.
- Provide circuit design so the reversing edge circuit can be checked by
pressing a test button inside the control panel..
- STANDARD AND FAIL-SAFE REVERSING EDGE CIRCUITRY
- Control circuitry will provide installation and operation of the standard
facility reversing edges or fail safe design reversing edges via
installation of one jumper wire at a terminal block location.
- Circuitry will be such that the Pilot light and reset button on the panel
face shall work for both types of edges.
- AUXILIARY PUSH BUTTONS
- The terminal strip shall contain provisions for at least two remote stop
pushbuttons in the control circuit, as well as the panel face stop button.
- Provisions shall be made for installation of remote open and close
buttons.
- DELAY TO REVERSE CIRCUIT
- Each panel shall have a delay to reverse circuit with adjustable time of
.1 to 1.9 seconds.
- As the door is closing, and any reversing or activation device is
activated, the door shall stop, the timer will activate and time out, and
then send the door to the fully open position.
- Circuitry shall be tied in with the brake circuitry to enable proper brake
operation.
- DOOR POSITION INDICATION
- Provide terminals at the terminal strip to indicate the door fully open or
fully closed.
- Contacts for each position - 1 NO and 1 NC
- OVERLOAD TRIPPED PILOT LIGHT
- Provide pilot light indication on face of control panel to indicate when
the thermal motor overload is in a tripped position.
- Pilot light is to be push to test design.
- Circuit design to incorporate remote reset capabilities for future
expansion and tie in with remote PLC systems, such as AGV’s, etc.
- MAIN CONTROL CIRCUIT VOLTAGE
- The main control circuit shall be operated at 24VAC to help reduce shock
hazard.
- Terminals shall be provided at the main terminal strip for access to 24
VAC for accessories.
- AUXILIARY DEVICE VOLTAGE PROVISIONS
- Provide a 120 VAC transformer in the circuit for accessory adaption.
- Terminals shall be provided for access to 120 VAC power for accessories.
- HAND / AUTO SELECTOR SWITCH
- Provide a selector switch on the panel face for sequencing as per the
"Sequence of Operations" section.
SEQUENCE OF OPERATIONS
- Power on - Selector Switch in HAND position.
- Door Fully Closed
- Momentary contact on the Open push button sends the door to the fully
open position.
- Momentary Contact open/close devices send the door to the fully open
position.
- Automatic open/timed close devices have no effect.
- External reversing devices have no effect
- Door Fully Open
- Momentary pressure on the close pushbutton starts the door closed.
- Momentary Contact open/close devices start the door closed.
- Automatic open/timed close devices have no effect.
- External reversing devices have no effect
- Door Moving Closed
- Momentary pressure on the stop button immediately stops the door.
- Open button has no effect
- Momentary Contact Open/Close devices stop, delay and reverse the door
to the fully open position.
- External reversing devices stop, delay and reverse the door to the
fully open position.
- Automatic open/timed close devices have no effect.
- Power on - Selector Switch in AUTO position.
- Door Fully Closed
- Momentary contact on the Open push button sends the door to the fully
open position.
- Momentary Contact Open/Close devices send the door to the fully open
position.
- Automatic Open/Timed Close devices send the door to the fully open
position.
- External reversing devices have no effect.
- Door Fully Open
When the door reaches the fully open position, and the open limit switch
is tripped, an automatic close timer is energized.
- Momentary contact on the Close push button sends the door down.
- Momentary Contact Open/Close devices send the door to down.
- Automatic Open/Timed Close devices reset the automatic close timer,
and the cycle begins timing from 0 seconds..
- External reversing devices reset the automatic close timer, and the
timing cycle begins timing from 0 seconds..
- Door Moving Closed
- Momentary pressure on the stop button immediately stops the door.
- Open button has no effect.
- Momentary Contact Open/Close devices stop, delay and reverse the door
to the fully open position.
- External reversing devices stop, delay and reverse the door to the
fully open position.
- Automatic Open/Timed Close devices stop, delay and reverse the door to
the fully open position.
- Reversing door edge stops, delays and reverse the door to the fully
open position. NOTE: The door will not automatically close until the
Reversing edge reset button is pressed.
|